DATA CENTER

Our server vendor maintains servers in the Largest Internet Service building in the world (over 350,000 sq feet)! This building hosts over 10,000 racks of servers. If uptime and reliability is important for you, you made the right choice.

Floor to Floor Height:

Typical floor: 4.1m (3.5m under beam)
Floor loading: 5kPa / 7.5 kPa
Typical Floor: 14, 000 sq feet gross
Number of Storey: 24 storeys of ISC's
Utility Connection

Dual 11kV power supply from seperate HKE zone substations
Dual feed telecom connection from seperate telephone exhanges (PBXs)
Electricity Supply

UPS (Uniterrupted Power Supply)
Main Supply: KVA Transformers
UPS: 400KVA UPS modules with n+l configuration per floor, 30 mins battery back up time, dual power supply risers
ESP:2000KVA generator sets ( 24-hour continuous full supply )
Earthing: Separate data centre clean earth
Industrial-Grade Air Conditioners

Indoor temperature at 20 +/- 2 Degree Celsius
Relative humidity at 50% +/- 10 %
Direct expansion type or Chilled Water Type CRAC unit
Stand By Servers

Spare servers are kept on-line of all CPU configurations. If a server were to experience a hardware failure, we would insert it into an identical standby CPU. We would then reboot the second machine and the server would be up and running again in a matter of minutes.

Network Reliability

Dual TBE rooms and dual risers
Dedicated 100mm dia G.I. Conduit for vertical backbone.
G.I. Conduit for interfloor cabling use
Optical fibre to the building